Product Features
ETA Module 17plus 3AC433V / E-T-A Abschlussmodul - Partsmax Türkiye
Thermal-Magnetic Circuit Breaker 2210-T2..
Issue D www.e-t-a.de 3 - 17
3
Description
Typical applications
Ordering information
Technical data
One, two and three pole thermal-magnetic circuit breakers with trip-free
mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934).
Featuring a combi-foot design for both symmetric and asymmetric rail
mounting. Available with auxiliary contact (1 x N/O or 1 x N/C) for status
signalling. Two and three pole models are internally linked to ensure that
both/all poles trip in the event of an overload on one pole, even if the
actuator is held in the ON position. This CBE can be supplied in current
ratings up to 32 A with a choice of characteristic curves. All screw
terminals are recessed for safety. Approved to CBE standard EN 60934
(IEC 60934).
Process control equipment, robotics, machine tool control,
communications systems, instrumentation.
2210-T2..
1-pole 3-pole
Type No.
2210 single and multipole thermal-magnetic circuit breaker
Mounting
T rail mounting
Actuator design
2 toggle
Number of poles
1 single pole protected
2 2-pole protected
3 3-pole protected
Accessories
0 without accessories
Terminal design (main contacts)
K0 screw terminals
Characteristic curve
F1 fast acting: therm.1.01-1.4xIN;
magn.2-4xIN DC (DC only)
F2 fast acting: therm.1.01-1.4xIN;
magn.3,5-6,5xIN AC/4,5-8,5xIN DC
M1 standard delay: therm. 1.01-1.4xIN;
magn. 6-12xIN AC, 7.8-15.6xIN DC
T1 delayed: therm. 1.01-1.4xIN; magn. 10-20xIN AC
Auxiliary contact design
H without intermediate position
Auxiliary contacts
1 with auxiliary contacts
2 auxiliary contacts on pole 1 only
(multipole devices)
Auxiliary contact function (see diagrams)
2 1 N/O contact
3 1 N/C contact
Auxiliary contact - terminal design
1 screw terminals
Current ratings
0.1...32 A
2210 - T 2 1 0 - K0 M1- H 1 2 1 - 10 A ordering example
For further details please see chapter: Technical Information
Voltage rating AC 250 V; 3 AC 433 V (50/60 Hz); DC 65 V
(UL: AC 277/480 V; DC 65 V)
Current rating range 0.1...32 A for curves M1, T1
0.1...16 A for curves F1, F2
Auxiliary circuit 1 A, AC 240 V / DC 65 V, resistive
Typical life
3 AC 433 V; AC 250 V: 0.1...25 A
10,000 operations at 1 x IN, inductive
DC 65 V: 0.1...32 A
10,000 operations at 1 x IN, inductive
3 AC 433 V; AC 250 V: 32 A
10,000 operations at 1 x IN, resistive
Ambient temperature -30...+60 °C (-22...+140 °F) T 60
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
main/aux. circuit AC 3,000 V
pole/pole AC 1,500 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity Icn 0.1...5 A 400 A
6...32 A 800 A
curves F1, F2, M1, T1: 0.1...16 A 2,500 A (at DC 32 V)
Interrupting capacity (UL 1077)
Degree of protection operating area IP30
(IEC 60529/DIN 40050) terminal area IP20
Vibration curves F1, F2: 3 g (57-500 Hz), ± 0.23 mm (10-57 Hz)
curves M1, T1: 5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock curves F1, F2: 25 g (11 ms), directions 1, 2, 3, 4, 5
10 g (11 ms), direction 6
curves M1, T1: 25 g (11 ms), directions 1, 2, 3, 4, 5
20 g (11 ms), direction 6
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass approx. 60 g per pole
IN 0.1...16 A 20...25 A
AC 277 V 1-pole 5,000 A 2,000 A
AC 277/480 V 2-/3-pole 5,000 A 2,000 A
DC 65 V 2,000 A 2,000 A
Preferred types Standard current ratings (A)
1-pole 0.5 1 2 3 4 5 6 8 10 16 20
2210-T210-K0M1-H121- x x x x x x x x x x x
2-pole 0.5 1 2 3 4 5 6 8 10 16 20
2210-T220-K0M1-H221- x x x x x x
Preferred types NEW
Thermal-Magnetic Circuit Breaker 2210-T2..
3 - 18 www.e-t-a.de Issue D
3
Installation drawing
Dimensions
M1
12A
Si-terminal M3
max. 1.5 mm2 (AWG 16) (rigid conductor)
tightening torque 0.5 Nm
.295
12-14
.472-.551
.354-.472
9-12
unit I
unit II
unit III
44
30.5
18
12.5 12.5
40
5.5
37.5
OFF ON
78.5 12.5
20
Si
1
Si
2
12
15
88.5
42.5
5.5
7.5
11.5
25 slot fitting labels from
Phoenix
Weidmüller
Wieland
G-profile
EN 50035-G32
symmetric rail
EN 50022-35x7.5
EN 50022-35x15/1.5
main contact terminal
max. 6 mm2 (AWG 10)
(rigid conductor)
tightening torque 0.5 Nm
M1
12A
45
.787
1.77
.217
1.67 1.57
.472
.591
toggles linked
for multipole
devices
11.5
.453
1.73
3.09
3.48
.709
.984
1.20
1.48
.453
.492 .492
.492
M1
12A
.217
Si
1
Si
2
operating area
(reinforced insulation)
mounting area
Standard current ratings and typical internal resistance values
This is a metric design and millimeter dimensions take precedence ( mm ) inch
Approvals
Authority Voltage ratings Current ratings
GL, VDE (EN 60934) 3 AC 433 V; AC 250 V;
DC 65 V
0.1...32 A
UL, CSA AC 277 V; AC 277/480 V;
DC 65 V
0.1...32 A
Current rating (A) Internal resistance (Ω)
F1 F2 M1 T1
fast acting
for DC only
fast acting
delay for
AC + DC
standard for
AC+DC
delayed low
resistance
for AC only
0.1 162 162 92 81
0.2 39.3 39.3 26.1 24.2
0.3 17.5 17.5 11.6 10.4
0.4 9.2 9.2 6.6 6.0
0.5 6.8 6.8 4.1 3.9
0.6 4.2 4.2 3 2.7
0.8 2.8 2.8 1.65 1.53
1 1.6 1.6 1.10 0.98
1.5 0.78 0,78 0.47 0.42
2 0.42 0,42 0.28 0.24
2.5 0.26 0.26 0.183 0.17
3 0.18 0.18 0.124 0.12
4 0.12 0.12 0.077 0.073
5 0.092 0.092 0.063 0.055
6 0.054 0.054 0.045 0.039
8 0.025 0.025 ≤ 0.02 ≤ 0.02
10 0.022 0.02 ≤ 0.02 ≤ 0.02
12 ≤ 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02
16 ≤ 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02
20 - - ≤ 0.02 ≤ 0.02
25 - - ≤ 0.02 ≤ 0.02
32 - - ≤ 0.02 ≤ 0.02
Thermal-Magnetic Circuit Breaker 2210-T2..
Issue D www.e-t-a.de 3 - 19
3
Trip time in seconds Trip time in seconds Trip time in seconds
-F1 0.1…16 A DC only
0.001
1 2 4 6 8 10 20 40
10000
1000
100
10
1
0.1
0.01
6080100
-F2 8…16 A AC/ DC 1)
10000
0.001
0.001
1 2 4 6 8 10 20 40
1000
100
10
1
0.1
0.01
6080100
1 2 4 6 8 10 20 40
10000
1000
100
10
1
0.1
0.01
6080100
-F2 0.1…7.5 A AC/ DC 1)
-30 °C
-22 °F +23 °C
+73.4 °F +60 °C
+140 °F
… times rated current
… times rated current
… times rated current
1) Magnetic tripping currents are increased by 30 % on DC supplies.
Internal connection diagrams Typical time/current characteristics
OFF position ON position
N/O contact
N/C contact
0 I 1 13
2
0 I 1 11
2
I >
0 I 1 13
2
0 I 1 11
2
line line
line line
(Si) (Si)
(Si) (Si)
(Si) (Si)
12 12
(Si) (Si)
14 14
I >
I >
I >
...-H131-...
...-H121-...
5 6
1
2
4
3
Shock directions
Thermal-Magnetic Circuit Breaker 2210-T2..
3 - 20 www.e-t-a.de Issue D
3
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the circuit
breaker current ratings by the derating factor shown below. See also section
Technical information.
Multi pole devices: all poles symmetrically loaded. With single pole overload,
thermal tripping will be at max. 1.7 x IN with curves F1, F2 and M1.
1) Magnetic tripping currents are increased by 30 % on DC supplies
(curves M1, T1). Ambient °F
temp. °C
-22
-30
-4
-20
+14
-10
+32
0
+73.4
+23
+86
+30
+104
+40
+122
+50
+140
+60
Derating factor 0.76 0.79 0.83 0.88 1 1.04 1.11 1.19 1.29
-T1 8…25 A AC only
100
10
1
0.1
0.01
0.001
Trip time in seconds
1 2 4 6810 20 40
10000
1000
6080100
… times rated current
100
10
1
0.1
0.01
0.001
Trip time in seconds
1 2 4 6810 20 40
10000
1000
6080100
… times rated current
-M1 0.1…6 A AC/DC 1) -M1 8…25 A AC/DC -T1 0.1…6 A AC only 1)
100
10
1
0.1
0.01
0.001
Trip time in seconds
1 2 4 6810 20 40
10000
1000
6080100
… times rated current
100
10
1
0.1
0.01
0.001
Trip time in seconds
1 2 4 6810 20 40
10000
1000
6080100
… times rated current
Typical time/current characteristics
Thermal-Magnetic Circuit Breaker 2210-T2..
Issue D www.e-t-a.de 3 - 21
3
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
Accessories
Art.-Nr. Y 308 498 01
IEC 664 500 V/100 A (40 °C)
Art.-Nr. Y 308 498 01
IEC 664 500 V/100 A (40 °C)
marking 4 x on busbar
79 x 12.5 = 987.5 12.5
3
4.6
14.7 1.5
30.7±0.4
16
Art.-Nr. Y 308 499 01
IEC 664 500 V/100 A (40 °C)
Art.-Nr. Y 308 499 01
IEC 664 500 V/100 A (40 °C)
marking 4 x on busbar
79 x 12.5 = 987.5
3±0.2
16
L2
L1
L2 L1
L1
L1
L2
L2
L1
L1
L2
L2
L1
L1
L2
L2
L1
L1
L2
L2
L1
L1
L2
L2
L1
L1
L2
L2
L1
L1
L2
L1
L2
L2
L1
995+2
995+2
15.8
33,3
17.3
±0.4
~2.76
Connector bus links -K10
X210 589 01/ 2.5 mm2, (AWG 14) (black) up to 20 A max. load
X210 589 02/ 1.5 mm2, (AWG 16) (brown) up to 13 A max. load
50 pin lugs to
DIN 46230
tinned copper
ø2.5
.099
~70
79 x 12.5 = 987.5
12.5
3±0.2
1.5
20-1
16-1
14.7 4.6
Busbar 1-pole, 90°
X 222 540 01
The one metre long busbars can be cut to suitable lengths.
Plug-on caps can be fitted on the ends to provide brush
contact protection.
Imax - busbar 100 A (40 °C)
.118±.008
.492
79 x .492 = 38.878
.579
.181
.059
.630-.039
.787-.039
.118
.492
79 x .492 = 38.878
79 x .492 = 38.878
39.173+.079
.630
.181 .579
1.209±.016
.059
39.173+.079
.630
12.5
.492
.118±.008
1.5
.059
.622
.681
1.311±.016
Elektrotechnische Apparate GmbH
D-90418 Altdorf bei Nürnberg
Elektrotechnische Apparate GmbH
D-90418 Altdorf bei Nürnberg
Busbar 1-pole
Y 308 498 01
Imax - busbar 100 A (40 °C)
Plug-on cap, 1-pole
Y 307 851 01
Busbar 2-pole
Y 308 499 01
Imax - busbar 100 A (40 °C)
Elektrotechnische Apparate GmbH
D-90418 Altdorf bei Nürnberg Elektrotechnische Apparate GmbH
D-90418 Altdorf bei Nürnberg
Plug-on cap, busbar 2/3-pole
Y 308 506 01
Plug-on cap, 1-pole
Y 307 851 01
This is a metric design and millimeter dimensions take precedence ( mm ) inch
Supply terminal
Y 308 503 01
Imax 63 A with 1-pole busbar,
50 A with multipole busbar
Max. tightening torque of terminal screw 2 Nm
Max. cable cross section: 25 mm2 / single strand
16 mm2 / multistrand
with wire end ferrule
Art.-Nr. Y 308 500 01
IEC 664 500 V/100 A (40 °C)
Art.-Nr. Y 308 500 01
IEC 664 500 V/100 A (40 C) °
marking 4 x on busbar
80 x 12.5 = 1000 12.5
3±0.2
L3
L1
L2
L2
L2
L3
L3
L1
L2
L2
L1
L3
L3
L1
L2
L2
L2
L2
L1
L3
L3
L1
L2
L2
L1
L3
L3
L1
L2
L2
L1
L3
L3
L2
L2
L2
1010+2
15.8
17.3
1.5
18.4
3
16.2
33.7
13
16
39.764+.079
.630
.492
118±.0082
80 x .492 = 39.370
.622
.681
33,3±0.4
1.311±.016
1.5
.059
.118 .059
.512
1.327
.638
.724
Elektrotechnische Apparate GmbH
D-90418 Altdorf bei Nürnberg Elektrotechnische Apparate GmbH
D-90418 Altdorf bei Nürnberg
Busbar 3-pole
Y 308 500 01
Imax - busbar 100 A (40 °C)
Plug-on cap, busbar 2/3-pole
Y 308 506 01
Caution:
When using multipole busbars please leave at least one pole’s
width between two adjacent line entry terminals. ETA Module 17plus 3AC433V / E-T-A Abschlussmodul - Partsmax Türkiye
------------------
One, two and three pole thermal-magnetic circuit breakers with trip-free
mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934).
Featuring a combi-foot design for both symmetric and asymmetric rail
mounting. Available with auxiliary contact (1 x N/O or 1 x N/C) for status
signalling. Two and three pole models are internally linked to ensure that
both/all poles trip in the event of